April 1996, Volume 5


Figure 1 depicts a typical aluminum or steel manufacturing process in which fugitive smoke must be evacuated from an enclosed area for health reasons. Escaping smoke from a furnace hood area can be captured if additional draft can be derived from the I.D. fan system or if the hood capture efficiency can be increased by implementing a design modification. Generally, only an increase in fan capacity lends for a practical solution to the fugitive smoke problems at the hood of the furnace or in the top ventilating area of the building.

Interestingly, Process Equipment Company became involved in such a problem at a large aluminum plant in 1995. Aluminum is manufactured from alumina in "pot lines", i.e., numerous individual furnaces which unfortunately generate fugitive smoke which must be evacuated through a ventilation system to a baghouse and scrubber.

Because of fan limitations, smoke was escaping from the hoods at the individual pots and was accumulating inside the building and activating smoke detectors in the upper area of the building. Process Equipment Company decided that the most practical solution to this problem was to modify the eight individual fans in order to gain additional capacity and subsequently prevent the smoke from accumulating inside the building.

These particular fans were approximately 30 years old and were of the airfoil design, a fan design which would not ordinarily be used for induced draft applications except that, in this case, a mechanical collector is utilized to collect the coarse particles which would otherwise wear out the relatively thin gauge construction of the airfoil impeller. Figure 2 illustrates the tipout procedure to increase the wheel diameter and gain additional fan capacity. Originally, the scope of the project was defined to us as one requiring additional flow capacity without the need for additional static pressure capability. This common request is basically correct except that the additional capacity through the system of this type cannot be realized without a fan modification which will yield some degree of pressure increase. Fluid moving through an existing dust collector, ductwork, baghouse, and scrubber cannot be increased without experiencing some increase in pressure drop. Subsequently, a decision was made to enlarge the fan rotors as shown in Figure 2 so that the 800 horsepower motors would be fully loaded and a gain in both pressure and flow could be realized.

Process Equipment Company initially measured the performance of the fans as summarized in Table 1. The exact design of the tip modification was concluded after these field measurements were evaluated. The cost to perform a field modification of this type is quite inexpensive as compared to the cost associated with completely replacing the fans. Table 2 is a summary of the modified fan performance after the field impeller modification was complete. You can see from Table 2 that the total flow was increased by about 20% and the static pressure head increased by this same amount.

ORIGINAL FAN TEST RESULTS PERFORMED 10/29/95 - TABLE 1
Fan No.Flow Rate - ACFMFan Pressure RiseFan EfficiencyMotor HP
1245,40213.680.5653
2274,80210.876.5611
3184,08110.236.9800
4267,1879.265.1594
5292,0398.265.8574
6277,2309.362.6648
7342,0728.261.7716
8185,90010.939.4808
TOTAL2,068,713

FAN TEST RESULTS AFTER MODIFICATION PERFORMED 1/17/96 TABLE 2
Fan No.Flow Rate - ACFMFan Pressure RiseFan EfficiencyMotor HP
1294,86815.188.0796
2329,94114.390.3800
3315,81614.791.8795
4293,65114.584.6792
5286,63513.582.6737
6282,85913.681.2745
7306,78113.582.8787
8309,66414.592.7762
TOTAL2,411,215

The increase in fan capacity eliminated the smoke accumulation problem inside the building and was achieved at a very affordable capital cost price level. Replacement fans and motors on a project of this type would have cost millions of dollars while the field tip out capital cost totalled a fraction of this amount.

For additional information on articles appearing in this newsletter, contact Process Equipment Company at (205) 663-5330 or E-mail to: information@process-equip.com




Return to the Newsletter Page.
Return to the Home Page.